Abstract
This paper presents a methodology to evaluate the contribution of wind farms (WFs) to the short-circuit level of high-voltage substations. The method relies on simplified equivalent WF models suitable for integration in commercial network-analysis software platforms. The developed WF models are especially suitable for integration in PSS/E and they can be incorporated in models of large power systems. The methodology can be applied to all kinds of WFs regardless of the type of the wind turbines used. Finally, the proposed models are verified through detailed simulations and a case study concerning short-circuit level calculation at all 150-kV and 400-kV buses of the Greek power system is presented. The relevant results are presented and general conclusions are extracted.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.