Abstract

This is the fourth paper in a series on the wind effects of parapets on low-rise buildings. This part focuses on alternative parapet geometries which can mitigate local (component and cladding) loading due to the formation of corner vortices. It was found that spoilers and porous perimetric parapets significantly reduce the loads for all areas in the corner, edge and interior zones considered. For solid parapets, raising the corner, or putting a slot in the corner are also beneficial when compared to uniform, continuous parapets. Removing the corner of a continuous parapet also lowers the loads as compared to isolated (single) parapets which end at the side wall, indicating that shortened isolated parapets could also be beneficial.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.