Abstract
The performance of natural draft dry cooling towers (NDDCTs) depends on the environmental conditions. Crosswind is known to have the most destructive effect, whereas the ambient temperature is marked as the next. A 3-D numerical model was developed to investigate the thermal performance of a single as well as three aligned units of NDDCTs under crosswind conditions. The computed results showed major discrepancies between computed velocity patterns and pressure fields around three aligned towers and those of the single tower due to windshield effect of neighboring cooling towers. The thermal performance losses for the single tower under crosswind showed higher values compared with those of towers in the aligned arrangement. The best thermal performance of three aligned NDDCTs was achieved when the crosswind was directed along the towers’ connection line.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Iranian Journal of Science and Technology, Transactions of Mechanical Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.