Abstract

A 420-kV gapped-core five-legged variable shunt reactor is modeled in the frequency range 5 Hz-10 MHz based on frequency sweep measurements and curve fitting using rational functions. Comparison with time-domain measurements at reduced voltage shows that the model can accurately predict the transient behavior of the shunt reactor, both for impinging overvoltages and circuit-breaker transient recovery voltages. Among the observations is that mutual coupling between the phases leads to a beat phenomenon in the reactor voltage following disconnection. Representing the shunt reactor by an LC parallel circuit leads to unrealistic results for steep-fronted incoming waves and high-frequency oscillating overvoltages, and for the attenuation of the transient recovery voltage following disconnection.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.