Abstract

This paper presents an efficient wavelet and neural network (WNN) based algorithm for distinguishing magnetizing inrush currents from internal fault currents in three phase power transformers. The wavelet transform is applied first to decompose the current signals of the power transformer into a series of detailed wavelet components. The values of the detailed coefficients obtained can accurately discriminate between an internal fault and magnetizing inrush currents in power transformers. The detailed coefficients are further used to train an Artificial Neural Network (ANN). The trained ANN clearly distinguishes an internal fault current from magnetizing inrush current. A typical 750 MVA, 27/420KV, ∆/Y power transformer connected between a 27KV source at the sending end and a 420KV transmission line connected to an infinite bus power system at the receiving end were simulated using PSCAD/EMTDC software. The generated data were used by the MATLAB software to test the performance of the proposed technique. The simulation results obtained show that the new algorithm is more reliable and accurate. It provides a high operating sensitivity for internal faults and remains stable for inrush currents of the power transformers.

Highlights

  • Power transformer is one of the most essential elements in the power system

  • This paper proposes a new wavelet and Artificial Neural Network (ANN) based three phase transformer protection algorithm to distinguish inrush currents from internal fault currents in three phase power transformers

  • The proposed relay can distinguish an inrush current from the internal fault current based on the d1 coefficients and send a trip signal if the d1 coefficient is high

Read more

Summary

Introduction

Power transformer is one of the most essential elements in the power system. Power transformer functions as a node to connect two different voltage levels. Distinguishing an inrush current from an internal fault current is still a challenging Power Transformer Protection problem. J. Computer Sci., 3 (6): 454-460, 2007 applied to single phase power transformer protection to distinguish internal faults from magnetizing inrush currents [7, 8]. This paper proposes a new wavelet and ANN based three phase transformer protection algorithm to distinguish inrush currents from internal fault currents in three phase power transformers.

Results
Conclusion