When the water filtration plant in Bellevue, Ohio experienced reduced hydraulic capacity, the ensuing investigation revealed large deposits of calcium carbonate in the plant's pipelines. Alternative solutions to the encrustation problem were main replacement and main cleaning. A high pressure, water‐jet technique was chosen for cleaning the encrusted pipelines. This article describes the jet head and other equipment employed in the process, which involved installation and use of a temporary piping and pumping facility between the recarbonation chamber and eight filters so that water service would not be interrupted. Water pressures of 1000 to 10,000 psi were pumped into the jet heads to clean out the pipelines. The work took 40 hours and cost $8800, a significant savings compared to the $40,000 estimate the city received for replacement of the pipeline and associated fittings.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.