Abstract
Abstract Fire is a disaster that must be avoided in various ways, one of them is by using a fire extinguishing system to prevent fire disaster. This study used the Semarang City Health Office (DKK) Building as a sample. The purposes of this research were; (1) to find out whether the application of the fire protection system at DKK Building has met the regulations and (2) to determine whether the water distribution in the fire protection system in the Semarang DKK Building is functioning properly as needed. Data collection methods in this study consisted of observation and literature study. The observation was used to find research data in the form of planning drawings on the building protection system and the literature study was carried out to obtain data in the form of standard tool specifications and rules for using tools in the protection system. This study also used an analysis method based on an application program called Epanet 2.0. The Epanet program was used to simulate a hydraulic model according to the fire protection system at DKK Building. The results of the analysis using the Epanet 2.0 show that the sprinkler system has met the needs based on the amount of water supply discharge and based on the required pressure. The underground tank volume of 150 m3 has met the requirements based on SNI 03-3989-2000. The pressure value for all sprinklers has met the requirements of SNI 03-3989-2000 with the smallest pressure value is 2.5 kgf / cm2. The sprinkler system does not meet the water distribution value set in NFPA 13 with a maximum distribution time of 50 seconds while the analysis results show that the distribution time is 205 seconds. The pressure value at all points of the fire hydrant system meets the SNI 03-1745-2000 rules with a maximum value not exceeding 24.1 bars. The pressure value at the farthest hydrant box hose connection does not meet the SNI 03-1745-2000 rules with the pressure value at the farthest hydrant box is 4.6 bars, where is the minimum pressure is 6.9 bars.
Highlights
Semarang City Health Office (DKK) building was built in the early of 2019, which has 3 main functions, as well as office, health center and a parking building
The 1st and 2nd floors are used for Puskesmas/ health center, 9th, 10th floor and basement are for the Health Office and 3rd - 8th floors are as parking area
Water availability, pressure and velocity in the fire protection systems must be able to extinguish each spot of fire in building area by manual or automatic systems [2]
Summary
Semarang City Health Office (DKK) building was built in the early of 2019, which has 3 main functions, as well as office, health center and a parking building. Fire is a thermo chemical reaction caused by oxygen, fuel, and heat. The products of fire cause disaster in the building area. Fire prevention activity in DKK Building uses automatic sprinklers system and hydrants. Water availability, pressure and velocity in the fire protection systems must be able to extinguish each spot of fire in building area by manual or automatic systems [2]. Putri [7] has examined the design and analysis of automatic sprinkler systems and firefighting hotels using manual calculations. Both studies only calculated the farthest point. We need the entire system pressure result to determine whether the pipe system meets SNI standards. It is expected to be able to encourage other facilities to improve the security in the form of a fire extinguisher system to functions precisely and efficiently
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.