Abstract

A packaged ammonia-water absorption chiller using a waste-heat stream and operating at severe ambient conditions is developed and experimentally evaluated. The chiller is designed to provide 2.6 kW of cooling at an ambient temperature of 51.7 °C. The system is directly coupled to exhaust gas from a diesel generator to drive the absorption cycle. The absorber and condenser reject heat directly to ambient air. Direct coupling to the heat source and the ambient heat sink leads to reduced system size and minimization of parasitic electrical power required for coupling fluid pumps. The dimensions of the unit are: 0.66 m × 0.61 m × 0.48 m (L × W × H). An autonomous control system is also developed and demonstrated experimentally. System performance is measured at ambient temperatures of 40–52 °C, delivering cooling duties of 2.5–1.8 kW, with overall coefficients of performance (COPs) of 0.38–0.3. Performance limitations and areas for future development are discussed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.