Abstract

An evaluation was made of the effects of radiant heat transfer from hot stove and chimney pipes to unprotected and protected room walls and ceilings. Pipe surface temperatures were 350° C (662° F) for normal operation, and 400–450° C (752–842° F) to simulate overfire conditions. Unprotected ceilings at 457 mm (18 in.) clearance met code recommended temperature rise limits for normal operation, but protection was needed for overfire exposures. Some protected walls allowed for clearance reductions to 76 mm (3 in.) for all exposures, while others needed at least 304 mm (12 in.) for normal and 457 mm (18 in.) for overfire exposures.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.