Abstract
Measurement units of high-frequency voltage transients have been specifically developed and installed at three different busses of an Italian medium voltage (MV) feeder, mainly composed by overhead lines and located in a rural region characterized by a high ground flash density (4flashes/km2/yr). Several of the recorded voltage transients in the period from March 2007 to August 2008 are correlated with specific events detected by the Italian lightning location system (LLS) CESI-SIRF and with sequence of protection operations recorded by the utility's data acquisition system. The paper presents the analysis of these correlated events. Moreover, the paper compares some voltage transient measurements with the computer simulation results obtained by a detailed LIOV–EMTP model of the MV feeder response to indirect lightning strokes. The aim of the paper is to provide elements useful to solve the problem of correlating line faults with lightning events.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.