Abstract

This paper reveals that the impedance match (or the Thevenin circuit) based voltage stability monitoring techniques have problems to predict voltage stability limits when applied to multi-load power systems. Power system loads are nonlinear and dynamic. They cannot be simply represented as Thevenin circuit parameters for impedance match analysis. To overcome these difficulties, a new concept called “coupled single-port circuit” is proposed in this paper. The concept decouples a meshed network into individual single generator versus single bus network and, as a result, a modified version of the impedance match theorem can be used. This leads to a real-time voltage stability monitoring scheme without the need to estimate Thevenin parameters. The scheme can estimate voltage stability margin and identify weak areas in a system based on the SCADA and PMU data. Case studies conducted on several test systems have verified the validity of the proposed method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.