This study presents optimisation based strategy to successfully control voltage stability of power systems using limited number of measurements. In a multi-area power system, Ward reduction based network is used to enhance the loadability margin of the overall system, based on measurements from the internal area only. Information regarding the recent changes in the external areas is considered in the reduced network through hybrid state estimator, to enhance the estimation accuracy of the system states. Predictor-corrector primal-dual interior point technique is used to optimise the loadability margin above a given critical margin. The voltages obtained for this optimised margin are used as target values for determining the actual control parameters, by means of Gauss-Newton optimisation. The proposed methods are successfully implemented on IEEE 30-bus and 118-bus test systems.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.