Abstract

A sound power system must have voltage values at all buses that do not exceed the tolerance limit of ± 5% with small power losses. Voltage instability can be caused by interference or sudden power generation outage from the system. Indonesia's Southern Sulawesi power system has been interconnected with wind power plants located in Sidrap Regency and Jeneponto Regency. Wind speed energy used by wind power plants to generate electricity vary and not always constant. Hence, this can cause fluctuations and produce varied outputs that will affect the voltage profile and stability of the Southern Sulawesi interconnection system. Therefore, it is essential to assess the voltage stability of the Southern Sulawesi power system after the integration of Sidrap and Jeneponto WPPs. First, this study analyzes the voltage profile of the Southern Sulawesi interconnection system voltage after integrating the Sidrap wind power plants and Jeneponto Wind Power Plant during the peak day load and peak night load. Second, the study assesses the voltage stability with a varied output power of both Sidrap and Jeneponto Wind Power Plant. After integrating Sidrap and Jeneponto Wind Power Plants, the results showed that the voltage values at all system buses are stable and within the IEEE standard (between 0.95 p.u. and 1.05 p.u.). In addition, the voltages of the Southern Sulawesi power system with various outputs of both WPPs are still stable and within the IEEE standard.