Abstract

In this paper, the effects of a superconducting fault current limiter (SFCL) installed in loop power distribution systems on voltage sags are assessed and analyzed. The power distribution system will be operated to a type of loop. In this case, voltage drops (sags) are severe because of the increased fault current when a fault occurs. If SFCL is installed in the loop power distribution system, the fault current decreases based on the location and resistance value of the SFCL, and voltage sags are improved. In this paper, the improvement of the voltage sag is analyzed according to the fault location, resistance value of SFCL, and the length of the loop power distribution system. First, a resistor-type SFCL model is used using the PSCAD/EMTDC. Next, the loop power distribution system is modeled. Finally, when the SFCL is installed in the radial or loop power distribution system with various lengths, voltage sags are evaluated according to various fault locations. The results of voltage sag analysis in the loop system are compared with the voltage sags in radial power distribution system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.