Abstract

AbstractThis paper proposes a voltage control method during service restoration in the distribution networks with photovoltaic (PV) generator systems. In the current distribution automation system (DAS) process in Japan, voltage dips and surges occur during service restoration because PVs are disconnected simultaneously after a fault and subsequently reconnected after service restoration. However, in the current DAS, voltage regulators such as an on-load tap changer (OLTC) and step voltage regulators (SVRs) are not controlled during service restoration. The proposed DAS estimates the voltage in a distribution network during service restoration, and it controls the tap position of OLTC and/or SVRs according to the predicted voltage. The numerical simulation results using a real-world distribution system model on a real map and PV output profiles derived by actual square kilometer solar radiation data will be shown. Those results indicate that the proposed DAS prevents voltage deviation that occurs as long ...