Abstract

In recent years, the number of connection of distributed generators (DGs) such as the photovoltaic generation (PV) and wind power generation is increasing, and there is in danger of changing the voltages in a distribution system by the precipitous output variation of DGs. In this study, the authors propose one voltage control method of a distribution system by the static var compensator (SVC) in consideration of cooperation with the load ratio control transformer (LRT) of laggard control response installed beforehand in the distribution system. The proposed method may be able to make the rated capacity of SVC small and may be able to reduce the aggravation of power factor of the distribution system, by setting up the dead band of voltage control appropriately. And the authors propose one determination method of the necessary minimum rated capacity and optimum control parameters of SVC in view of the cost of equipment and high-speed controllability. In order to verify the validity of the proposed method, the numerical calculations are carried out by using a distribution system model.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.