Abstract

In this paper, a novel technique to balance the voltage of the two split dc capacitors of a 3-Level neutral-point-clamped inverter using triangular carrier pulse width modulation is presented. This technique, suitable for reactive power compensation and for inverters operating with a relatively low switching frequency, consists in adding a square wave at six times the output frequency. Subsequently, this paper presents a comparison with two already known strategies in which a sinusoidal waveform at two and six times the output frequency are injected. The current contribution to the midpoint of the dc bus is then analyzed for different modulation indexes and operating conditions. Based on this analysis, a small-signal averaged model, suitable for control design purposes is presented. Finally, simulation and experimental results on a 690-Vac, 120-kVA test bench that validate the theory are shown.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.