Abstract

This paper investigates voltage and reactive power control in distribution systems and how the presence of synchronous machine-based distributed generation (DG) affects the control. A proper coordination among the onload tap changer (OLTC), substation switched capacitors and feeder-switched capacitors in order to obtain optimum voltage and reactive power control is proposed. It is assumed that there is no communication link between the OLTC and the capacitors, a normal case in distribution system operation these days. The results indicate that the proposed method decreases the number of OLTC operations, losses, and voltage fluctuations in distribution systems, with and without DG present. The power-flow reversal due to the DG is shown not to interfere with the effectiveness of the OLTC operation. Further, it is also shown that as long as the available capacitors are enough to compensate the reactive power demand, the DG operation mode does not give a significant effect to the distribution system losses. However, DG operating at a constant voltage is beneficial for a significant reduction of OLTC operation and voltage fluctuation in the distribution system.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.