Abstract

This letter exhibits the presence of High-Frequency (HF) current signatures of arcing in Vegetation High Impedance Fault (VeHIF) events. Zero-crossing arcing discontinuities are shown to have varying widths causing different levels of HF noise bursts depending on how aggressively the 50-Hz waveform gets distorted. The work has identified that the temporal growth in HF disturbances often occurs quicker than those linked to the third harmonic or the entire Low-Frequency (LF) spectrum. In 59.2 % of a dataset of 125 phase-to-earth (ph-to-e) faults, the growth in HF spectrum was identified to occur faster than the third-harmonic or the entire LF spectrum. The HF spectrum had an average lead time of 26.58 s over the LF spectrum. The LF indicator performed better in only 15 tests (12 %) with an average lead time of 9.6 s. In 13 tests (10.4 %), all three indicators concurrently reached the set normalized threshold.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.