Abstract

Using supplemental energy dissipation devices into the structure to increase the damping ratio for reducing the responses of seismic activity has become more and more popular. This paper presents a case study of seismic retrofit strategy, utilizing a type of passive energy dissipation device, namely, the viscous damper, in order to make an ongoing chips produced facility resistant to seismic activity. The building in question was a chips produced facility belonging to a semiconductor manufacturing company. This was a double FAB where the structure system was divided into an island building and an RC shell. The retrofit involved installing 44 non-linear dampers between the island building and the RC shell. This was due to the significant differences in the fundamental vibration periods. This paper will present the rationale of making a decision on the parameters of the dampers to give the optimum retrofit strategy.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.