Abstract

The overcurrent and overvoltage of the rotor side converter are mainly caused by the transient component of the stator flux under the grid symmetrical fault. A virtual transient flux linkage control method is proposed in this paper, which is based on the analysis of the electromagnetic transient characteristics of doubly fed induction generator (DFIG). Compared with the traditional demagnetization control method, the proposed method does not require the flux linkage observation, extraction and fault switch module. Simulation results show that the rotor voltage could be effectively limited and the transient process can be shortened, and the capability of low voltage ride through (LVRT) of the DFIG is enhanced with the proposed method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.