Abstract

Harmonic filters for a static VAr compensator (SVC) suppress power frequency harmonics generated by the nonlinear characteristic of the thyristor controlled reactors and electric arc furnace loads. SVC filters also provide the 60 Hz capacitive current needed by the SVC to reduce bus voltage flicker. Following reactor and capacitor failures the reliability of the SVC filter was improved. The first step was to measure the SVC filter stresses which was performed using a virtual instrument. The measurement equipment consisted of a personal computer equipped with two analog-to-digital (4/D) input boards, two signal conditioning input boards, and commercially available instrument and control software capable of configuring these basic hardware components for user defined instrumentation and analysis. Virtual instruments were used to sample, store, analyze, and display 32 channels of high speed data for 55 minutes of the combined furnace heat cycle. The author discusses the virtual instrument software, measurement and analysis technique, and statistical analysis. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.