Abstract

The Challenge to stabilize the grid frequency increases with the increment of renewable energy resources. System inertia/frequency control is a significant concern for maintaining system stability with a fast response time during the load transition. This manuscript proposes surface-mounted permanent magnet synchronous generator (SPMSG) based wind energy conversion system (WECS) with a frequency support DC-link controlling loop and a converter protective DC-link voltage-controller frequency support system. To achieve power exchange, the frequency control system (FCS) for the SPMSG-based wind turbine supports the grid-side virtual inertia. The DC-link voltage is disturbed during the load transition to maintain the frequency, while the electrolytic capacitor requires extra care regarding the DC bus voltage. This manuscript incorporates the FCS system with a supercapacitor and dynamic voltage limiter to avoid additional care of the DC bus voltage. A detailed analysis of system frequency with the additional load increment, normal connected load decrement, and various fault scenarios has been done. The proposed system is compared with the existing virtual inertia support (VIS). The simulation results show that the proposed frequency control system-based VIS efficiently limits the frequency deviations & DC-link voltage. The results are verified in the OPAL-RT 4510 real-time simulator environment to ensure the efficacy of the proposed system.