Abstract

An onload tap changer (OLTC) in suitable conditions is essential for the operation of a power transformer. It is extremely desirable to have indicators that help assess the conditions of the OLTC, especially if these indicators can be used in an on-line monitoring system that does not affect the normal operation of the transformer. This paper describes a method for detecting faults in the tap selector by means of vibration measurements during tap changer operation, using envelope analysis based on Hilbert transform and wavelet decomposition. Different failures at the tap selector can be distinguished in the vibration signature as they are reflected in different parts of that signature. The diagnosis parameters allowing the most selective failure classification are found.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.