This paper presents the results of Very Fast Transient Overvoltage (VFTO) computations that have been carried out using EMTP for various switching conditions in a 420 kV gas insulated substation. The variation of VFTO peak along the nodes for disconnector and circuit breaker operations as well as the variation of VFTO with different trapped charges have been studied. The results indicate a distinct pattern of variation of VFTO peak along the nodes of the GIS in the case of disconnector switch operation as compared to that of circuit breaker operation. It has also been noticed that the variation of VFTO peak levels are not proportional to the increase in the trapped charge.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.