Abstract

Cross-linked polyethylene (XLPE) power cable is commonly used as the medium for transmitting power supply in the power system network. However, frequent exposure of XLPE cable to the high voltage causes its insulation to degrade over time leading to electricity outages. Degradation of cable can be prevented if regular maintenance is performed using the accurate assessment method. This study models and simulates a cable system comprising of three cable sections connected by two un-degraded cable joints. This model aims to assess defect along the tested cable with the application of time domain reflectometry (TDR) technique. A series of simulations are conducted by varying the cable insulation condition to study its influence on the cable joint reflection. These simulation results from MATLAB/Simulink are validated against the actual TDR experimental results. The identical results shown between the simulation and experimental results indicate that the cable model is valid and can be used to assess the condition of a cable.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.