Abstract

In this paper, the model of chiller power consumption is built by using the regression analysis. While taking the parameters from the operation data of chiller into consideration simultaneously, i.e. Partial Load Ratio (PLR), chilled water supply temperature and cooling water return temperature, the prediction results are quite accurate, and its accuracy reaches over 99% in short-term prediction when compared with the actual power consumption. This method can be used to validate the benefits of the chiller’s energy saving method. The validation items include: the effect of water flow change on chiller’s performance while multiple chillers operate in parallel; the power consumption analysis of centrifugal chiller operating with or without frequency conversion; as well as the discussion on whether the cleaning of condenser coil can improve the Coefficient of Performance (COP) of chiller or not. The case study results show that, while multiple chillers operate in parallel, the water flow change has limited effect on the performance of chiller. However, about 36% electricity can be saved averagely when the chiller controls the frequency of electric power source at partial load, and the cleaning of condenser coil can increase the COP by 3.08%.

Highlights

  • IntroductionThe mankind has been relying on the energy. In recent years, with the vigorous development at home and abroad, the refining industry successfully expands the overseas oil market, and the import volume of industrial coal, electricity-generating natural gas and crude oil required by petrifaction are increased to a large degree, as a result, our energy supply has been growing obviously

  • Since the industrial revolution, the mankind has been relying on the energy

  • While taking the parameters from the operation data of chiller into consideration simultaneously, i.e. Partial Load Ratio (PLR), chilled water supply temperature and cooling water return temperature, the prediction results are quite accurate, and its accuracy reaches over 99% in short-term prediction when compared with the actual power consumption

Read more

Summary

Introduction

The mankind has been relying on the energy. In recent years, with the vigorous development at home and abroad, the refining industry successfully expands the overseas oil market, and the import volume of industrial coal, electricity-generating natural gas and crude oil required by petrifaction are increased to a large degree, as a result, our energy supply has been growing obviously. This study builds the power consumption model with linear regression to forecast the chiller’s power consumption, so as to discuss the effect of water flow change on the chiller’s performance and analyze the energy consumption of drive chiller in either variable frequency or invariable frequency mode. It validates the performance improvement before and after cleaning the condenser of chiller and the discussion of energy saving potential

Effect of Water Flow Change on Chiller’s
Variable-Frequency Chiller
Findings
Improvement of Chiller’s Performance by Cleaning the Condenser Coil
Conclusion
Full Text