Abstract

The overpressure generated in a 10 L cylindrical vented vessel with an L/D of 2.8 was investigated, with end ignition opposite the vent, as a function of the vent static burst pressure, Pstat, from 35 to 450 mb. Three different Kv (V2/3/Av) of 3.6, 7.2 and 21.7 were investigated for 10% methane–air and 7.5% ethylene–air. It was shown that the dynamic burst pressure, Pburst, was higher than Pstat with a proportionality constant of 1.37. For 10% methane–air Pburst was the controlling peak pressure for K <∼8. This was contrary to the assumption that Pred > Pburst in the literature and in EU and US standards. For higher Kv the overpressure due to flow through the vent, Pfv, was the dominant overpressure and the static burst pressure was not additive to the external overpressure. Literature on the influence of Pstat at low Kv was shown to support the present finding and it is recommended that the influence of Pstat in gas venting standards is revised.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.