Abstract
The occurrence of unstable subsynchronous control interaction (SSCI) between wind farms and series-compensated networks poses a considerable threat to the safety of power system. Different from the conventional eigenvalue analysis and Nyquist method, the black-box-model based RLC fitting technique becomes more attractive for the assessment of the SSCI risk. However, the method has merely been verified by radial networks whose SSCI mode can be well explained by an RLC circuit. A practical wind power system, however, can be meshed networks comprising multiple geographically distributed wind farms and series capacitors. Thus, it is questionable whether the application of the RLC fitting technique to such systems can still yield a sufficient accuracy. To clarify this aspect, in this work, the performance of RLC fitting in various test systems was examined. The results indicated that the aggregation technique considerably influences the accuracy of the assessment, and the RLC fitting cannot be applied when multiple series capacitors are involved in the SSCI mode. To address this problem, a more advanced frequency-domain fitting technique known as vector fitting was adopted, and its robustness and effectiveness were verified considering a modified The Electric Reliability Council of Texas (ERCOT) system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.