Abstract

Connection of offshore wind farms to shore requires the use of submarine cables. In the case of long HVAC connections, the capacitive charging currents limit the transfer capability and lead to high losses. This paper shows that the losses can be substantially reduced by continuously adjusting the cable operating voltage according to the instantaneous wind farm power production.Calculations for a 320 MW windfarm connected to shore via a 200 km cable at 220 kV nominal voltage shows that an annual loss reduction of 9 percent is achievable by simply using a 15 percent tap changer voltage regulation on the two transformers. Allowing a larger voltage regulation range leads to further loss reduction (13 percent for 0.4-1.0 p.u. voltage range). If the windfarm has a low utilization factor, the loss reduction potential is demonstrated to be as high as 21 percent . The methodology can be applied without introducing new technology that needs to be developed or qualified.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.