Abstract

The paper deals with the analysis of automatic generation control (AGC) of a two-area reheat thermal system considering a variable structure controller (VSC) based on the sliding mode concept. A systematic method is suggested for obtaining switching hyperplanes. Optimum gain settings of the variable structure controller are obtained, both in the unconstrained (neglecting generation rate) and the constrained (considering generation rate constraint) modes, using the integral squared error (ISE) technique. Investigation reveals that there is a significant improvement in system dynamic performance with a VSC over that with an integral controller. Moreover, the variable structure controller is found to be quite insensitive to wide variations of system parameters.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.