Abstract

Oak Ridge National Laboratory is developing a web tool, built on a rule-based expert system, that aids stakeholders in designing energy-efficient moisture-durable walls. Currently, the tool’s expert system database is mostly populated with expert opinion, but work is being done to incorporate durability assessment based on stochastic hygrothermal modeling. Chamber experiments have been conducted to validate the hygrothermal models. The measured temperature and humidity have been compared with those predicted by the hygrothermal model. Experiments and comparison to one-dimensional hygrothermal modeling results were completed with two walls, a Structural Insulated Panel (SIP) based wall and a Concrete Masonry Unit (CMU) based wall. The two walls were succumbed to typical Chicago weather in ORNL’s Heat, Air and Moisture chamber. The walls were sequentially exposed to different scenarios, including diffusion, wetting, air leakage and solar radiation. For the most part, the hygrothermal simulations can be successfully used to predict the performance of these wall systems for the moisture transport phenomenon. Errors between measured and simulated values decreased as measurements got closer to the interior side of the wall. The root mean square error was larger for relative humidity (up to 17.5%-RH for CMU) than for temperature (up to 4.5°C for CMU wall). The errors were larger for the CMU wall than the wood frame wall. The phenomenon, including liquid water, caused large discrepancies between measurement and simulation results, and simulated results showed slower drying of materials than measured results. The one-dimensional nature of the simulation model made simulating air leaks difficult but not impossible.

Highlights

  • Buildings accounted for 41% of the primary energy consumption (40.2 quads of energy) in the United States in 2010 [1]

  • This paper presents results from eight experiments, and the results are compared with hygrothermal modeling results

  • Considering that generic material properties were used for the Concrete Masonry Unit (CMU) block, the simulated temperature agrees well with the measured ones

Read more

Summary

Introduction

Buildings accounted for 41% of the primary energy consumption (40.2 quads of energy) in the United States in 2010 [1] Of this energy, 15.1 quads were consumed by the space heating and cooling of commercial and residential buildings [1]. 15.1 quads were consumed by the space heating and cooling of commercial and residential buildings [1] Of this amount, 5.8 quads are attributable to roofs and walls and 4 quads to infiltration. 5.8 quads are attributable to roofs and walls and 4 quads to infiltration Based on these data, reducing thermal conduction and increasing envelope airtightness are key factors in reducing the energy consumption in buildings. According to Building America, high-R wall assemblies (walls >R-30) have many hours throughout the year when condensation can potentially form inside the wall [2]

Objectives
Methods
Results
Conclusion
Full Text
Published version (Free)