Abstract

AbstractFire protection is a popular solution to slow down the temperature increase in steel elements subjected to fire, and simple equations, such as the mass lumped formula proposed in EN1993-1-2, may be employed to estimate the steel temperature in the cross-section. The EN1993-1-2 formula assumes that the temperature of the exposed insulation surface and the surrounding gas are equal. This simplification may provide inaccurate results for heavily insulated steel sections. Therefore, a new mass lumped formula was derived, accounting for more accurate boundary conditions considering the heat flux impinging the insulation. On these premises, this work evaluates how the new simple formula fares with respect to the EN1993-1-2 formula. In this respect, a comprehensive comparison with the results of 1-D and 2-D analyses considering several insulation materials and thicknesses of insulation and steel is thoroughly presented. The proposal results in being always safe and better estimates steel temperatures relevant in the structural fire engineering context. Its use is particularly recommended for heavily insulated sections, where the ratio between the insulation and the steel heat capacities is higher than 14, and the EN1993-1-2 formula gives unsafe predictions.