Abstract

This paper studies the possibility of using heat pump instead of cooling tower to decrease temperature and recover waste heat of circulating cooling water of power system. Making use of heat transfer theory the paper carried on analysis and calculation about recoverable waste heat of circulating cooling water in hot-stamping power system which includes hot-stamping, closing in and extrusion intermediate frequency induction furnace. The results show that the whole process can recover calories which is 2.642×106kJ per hour.Using the recycled calories can make 15.82 tons hot water per hour which is 60°C. This research shows that using heat pump to recover the waste heat of circulating cooling water is effectual.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.