Abstract

With the help of GPS signals for synchronization, increasingly ubiquitous phasor measurement units (PMUs) provide power grid operators unprecedented system monitoring and control opportunities. However, the performance of PMUs is limited by the inherent deficiencies in traditional transformers. To address these issues, an optical sensor is used in PMU for signal acquisition to replace the traditional transformers. This is the first time the utilization of an optical sensor in PMUs has ever been reported. The accuracy of frequency, angle, and amplitude are evaluated via experiments. The optical sensor based PMU can achieve the accuracy of 9.03×10−4Hz for frequency, 6.38×10−3rad for angle and 6.73×10−2V for amplitude with real power grid signal, demonstrating the practicability of optical sensors in future PMUs.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.