Abstract

In this paper, the analysis of magnetic field distribution of overhead mixed power line (20 kV/0.4 kV) supported by reinforced concrete towers, named MNL-12 is presented. The impact of ferromagnetic, conductive parts of the pylons (reinforcing bars, billets and cross arm beams) on magnetic field distribution is investigated. The numerical calculations were performed in COMSOL Multiphysics program package on simplified 2D model. The main goal of the calculations was to examine the impact of currents induced in ferromagnetic conductive parts on magnetic field produced by currents in the power system’s conductors. The calculation results are presented graphically, as the diagrams of the magnetic flux density magnitude distribution in the tower plan, normal to the system’s axe. The calculation results demonstrated that the magnetic field of induced currents decreases the magnetic field produced by the currents of overhead power system.