Abstract

In order to further investigate the vibration performance of power transformer for the detection of winding deformation based on the vibration frequency response analysis (VFRA) method, the electro dynamic forces of the winding of power transformer are calculated first by virtue of the field-circuit coupled finite element method. Then the axial vibration model of the winding is built and the harmonic response analysis is done to study the vibration performance with the obtained results of electro dynamic forces when the winding is in healthy condition and in fault condition. The experiment of vibration frequency response for the 220kV transformer is made via the developed vibration measurement system. Calculated results and experimental results are agreed well when the winding is deformed with the preset fault of the drop of winding block. Moreover, it is verified again by the experimental results that the vibration analysis method to detect the winding deformation is more sensitive than that of leakage reactance method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.