Abstract

AC electric arc furnaces (EAFs) are among the most common technological units for making high-quality steel. The use of furnaces is promising in the future as the production volumes of electric steel increase. These furnaces are powerful electrical installations exposed to the dynamic, asymmetrical, and nonlinear load, which adversely affects the quality indicators of electricity supply. Typically, this negative impact is reduced by connecting EAFs to high power energy systems or, in most cases, by applying different types of static reactive power compensators. Such approaches require considerable investment in the development of the power system or in the equipment of compensatory installations whose rated capacity is several times higher than the capacity of the furnace transformer. These approaches aim to reduce the effects of negative impact. It is possible to achieve the greater effect of limiting the negative impact, at smaller investments, by using an alternative approach that aims directly at the source of the negative impact. The approach implementation implies forming an external characteristic of the EAF power supply. The characteristic should be rigid in current in the region of furnace operating modes from operational short circuit to the rated load. In the region of modes from the rated load to idling, this characteristic should be rigid in voltage. Underlying the formation of this characteristic is a resonance converter, which ensures almost a stable value of the arc current under the furnace operating modes. This study has confirmed the significant benefits of the proposed approach, which proves more effective in improving the quality of electricity in the network. This makes it possible to use EAFs in smaller power systems and ensure the development of the industry at a lower investment

Highlights

  • IntroductionMost electrical energy receivers have a range of normal operating modes in the interval from idling to the rated load

  • Most electrical energy receivers have a range of normal operating modes in the interval from idling to the rated load. Connecting such installations to a power supply network whose voltage is supported almost constant at U=const ensures their high performance and electromagnetic compatibility with the network

  • We report the results of studying a conventional furnace power supply scheme (CSC) and a scheme involving the “constant current – constant voltage” converter (CC-CVC)

Read more

Summary

Introduction

Most electrical energy receivers have a range of normal operating modes in the interval from idling to the rated load Connecting such installations to a power supply network whose voltage is supported almost constant at U=const ensures their high performance and electromagnetic compatibility with the network. For the purpose of certain adaptation of such electric receivers to a conventional power supply network at U=const, a certain restriction of currents of operational short circuits to 1.8–2.5 relative units is imposed Such a technique involving low-power installations resolves to a certain extent the issue of electromagnetic compatibility under conditions of dynamic loading; their performance indicators and operational characteristics are compromised. The steady current under the modes of loading and operational short circuits leads to a decrease in the dynamic forcing on the equipment of the furnace installation and makes it possible to simplify its elements design

Literature review and problem statement
The aim and objectives of the study
Mathematical and MATLAB Simulink models of the compared schemes
Characteristics of the dynamic modes of the
15 Pst 12
Findings
Conclusions