Abstract

Classical differential protection schemes are subject to ghost differential currents due to CT saturation and magnetization currents. Several methods are used to counter the impact of these un-wanted differential currents. This paper will focus on using the symmetrical component techniques to stabilize differential protection schemes without sacrificing the speed and sensitivity of the protection. Negative sequence quantities are inherently present in any power system disturbances. Even in the case of a three phase symmetrical fault, negative sequence currents are present during the first few cycles of the fault as a result of the dc component. By accurately measuring the magnitudes and relative phase angles of the negative sequence currents leaving and entering into the differential zone can provide a very reliable indication of whether the fault is inside or outside of the protection zone. In addition, it can supplement the traditional restrained differential protection to achieve high levels of speed with very high sensitivity for high impedance faults. In transformer protection, turn to turn faults at the neutral points are typically difficult to detect. By using negative sequence quantities, these faults can be detected reliably.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.