Abstract

The article provides a brief background on the fundamentals of short-circuit analysis. Following that background is a discussion of how various types of phase overcurrent protective devices respond to the short-circuit current waveform. Based on this discussion, the short-circuit currents which are necessary to perform a protective device coordination study are specified. A comparison of the two types of short-circuit studies follows, based on the complex impedance network representation of the power system. The results of the comparison are then used to present recommendations for how the results of a computer-aided study to compute short-circuit current duties can be applied to determine the short-circuit currents necessary to select the settings of phase overcurrent protective devices. Finally, a sample industrial power system is provided to clarify the recommendations.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.