Abstract
This paper demonstrates that the direct wave of a radar ground-coupled antenna may be used for the nondestructive assessment of the physical condition of concrete, which directly influences the corrosion of the reinforcing bars in the structure. The validity of this method was evaluated by a comparison with the electrical resistivity method, which is frequently used for the evaluation of corrosion probability. Both methods were implemented in the laboratory on 72 concrete samples (25 × 25 × 8 cm 3) with various degrees of saturation and chloride contamination levels. On-site investigations were also carried out on the concrete slab (1080 m 2) of a car-park. The results of the laboratory tests show that the radar direct signal is strongly affected by variations in concrete moisture and chloride contamination level. The tests performed in real conditions confirm the good correlation between radar direct wave attenuation and electrical resistivity and, thus, the aptitude of the radar direct wave to detect concrete conditions leading to reinforcement corrosion.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.