Abstract

An analytical method is demonstrated which allows the level of negative phase sequence (NPS) voltage at a busbar to be expressed as a sum of phasors representing independent sources. The method is extended to enable the balancing capability of Static VAr Compensators (SVCs) with individual phase voltage control to be assessed. The capability of such SVCs and the allowable levels of NPS voltage on the system, including any short term limits, can be combined in a capability chart showing the unbalanced loads which can be supplied from a substation. The approach facilitates the treatment of fixed unbalances due to filters or intentional offsets designed to maximise the SVC balancing range for specific loads. Field test results are presented which validate the analytical methods used. >

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.