Abstract
This study proposes a novel scheme using mathematical morphology to effectively discriminate between the internal fault and inrush currents of power transformers. The proposed scheme consists of two parts. The first part is based on morphological gradient (MG), for discrimination of currents occurring without considering the current transformer (CT) saturation. The second one uses a symmetrical criterion involving MG to identify internal fault current under CT saturation. To demonstrate its compatibility and efficiency, the scheme is verified employing the data simulated using PSCAD/EMTDC and data collected from laboratory experiment, respectively. The simulation and experimental results indicate that the proposed scheme can improve the accuracy of inrush current identification, even under certain extreme conditions.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.