Main-tie-main (MTM) transfer schemes increase reliability in a power system by switching a load bus to a secondary power source when power interruption occurs on the primary source. Traditionally, the large number of physical I/O lines required makes MTM schemes expensive to design and implement. Using Ethernet-based IEC 61850, these hardwired I/O lines can be removed and replaced with generic object-oriented substation event (GOOSE) messages. Adjustment of the scheme for optimal performance is done via software that saves redesign and rewiring times. Special attention is paid to change-of-state GOOSE only; no analog GOOSE messages are used, making the scheme fast and easy to configure, maintain, and troubleshoot. Applications such as fast motor-bus transfer are discussed with synchronization remaining at each breaker relay. Simulation test results recorded GOOSE message latencies on a system configured for an MTM scheme. This paper presents the details of open and closed manual and automatic transfers.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.