Abstract

Estimating the proximity of power systems to voltage collapse in real time still faces difficulties. Beside the data management and computational issues, any central control method is subject to the reliability of long-distance data communications. In the paper, the authors describe a new data processing method to estimate the proximity to voltage collapse. The method (code-named SMARTDevice, for Stability Monitoring And Reference Tuning Device) employs only local measurements-bus voltage and load current-and calculates the strength of the transmission system relative to the bus. The collapse occurs when the local load approaches this value. The method is simple enough so that it can be implemented in a numerical relay. The performance of SMARTDevice is compared against the conventional undervoltage relay. It is shown that the latter can misoperate while the new device does not. SMARTDevice is in fact a new breed of voltage relays whose setpoint is automatically tuned to the system condition.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.