Abstract

Activation energy is popularly used for the estimation of remaining life of transformer insulation. It is defined as the average rate of all reactions that happen with cellulose. Existing literature shows that the activation energy of oil–paper insulation can be obtained from polarization depolarization current (PDC) and return voltage measurement (RVM) data that are measured at a specific temperature. It is practically difficult to ensure the same measurement temperature for both PDC and RVM data. On the other hand, PDC data and its analysis get influenced by de-trapping current. This de-trapping current is generated by ionic charge carriers that get freed from trap sites during PDC measurement process. Formation of these trap sites is related to physical, chemical reactions that happen at oil–paper interface. This paper proposes a methodology which uses de-trapped charge, dislodged from deep and shallow traps, to assess insulation condition and for the prediction of activation energy. Thus, eliminating the need of RVM data. The proposed method is tested using data collected from various real-life in-service transformers.