Abstract

In this paper an expansion cascade refrigeration system are compared to cascade systems using ejectors. This comparison is made for a variety of fluids. Natural fluids and hydrofluorocarbons (HFCs) are used in the two loops. Theoretical models are written using FORTRAN. The thermodynamic parameters of fluids are given using the software REFPROP 8.0. For fixed working conditions, using CO2, R23 or R32 in LPL and R152a in HPL in an expansion cascade system gives the best Coefficient of Performance (COP) which attains 1.57 for Ti = −15°C. A comparison between the different systems with ejectors showed that a cascade system with two ejectors is the most powerful. It allows an optimum COP equal to 1.8 and a relative performance equal to 19.8% when propane is used in HPL and CO2 in LPL for Ti = −25°C. But the best relative performance is given when R125 is used in HPL; it attains 24.2% when CO2 is used in LPL. An exergetic analysis shows that introduction of two ejectors in cascade system ameliorate the exergy efficiency by 27.3% when CO2 is used in LPL and R152a in HPL for Ti = −30°C.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.