Abstract

The present study investigated the efficacy of a physical water treatment (PWT) technology using catalytic materials to mitigate mineral fouling in a heat exchanger. The fouling experiments were conducted using hard water with an electrical conductivity of 3600 μmhos/cm. The effects of three different velocities (0.3, 0.5, 0.8 m/s) on the performance of PWT using catalytic materials were examined. The present results showed that PWT decreased the fouling resistances by 17% to 38% depending on the flow velocity. Furthermore, SEM photographs revealed that treated cases produced a calcite form of scale, which can be easily detached by flow shear forces.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.