Abstract

This article presents an investigative study on the efficacy of a new physical water treatment technology using an oscillating electric field to mitigate mineral fouling in heat exchangers. Parallel graphite electrode plates immersed in water were used to generate the electric field directly in water. Artificial hard water at 500 ppm hardness was used in all fouling tests. The inlet temperatures were maintained at 23.5 ± 0.5°C and 85 ± 0.5°C for cold- and hot-water sides, respectively. The results at a cold-water side velocity of 0.3 m/s showed a 16–60% drop in fouling resistances from the baseline test, depending on the frequency of the electric field for the physical water treatment-treated cases.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.