Abstract

Physicochemical treatment efficiency for unrestricted urban water reuse was evaluated at a conventional activated-sludge wastewater treatment plant (WWTP). Pilot plant set-up consisted of an alum coagulation step, granular media upflow flocculation and direct downflow dual-media filtration followed by ultraviolet disinfection (dose of 95 mJ cm⁻²). Optimum aluminum sulfate dosage of 10 mg L⁻¹ and coagulation pH 7.0 were preset based on bench scale tests. Under WWTP stable operation, water quality met United States Environmental Protection Agency (USEPA) suggested guidelines for unrestricted urban reuse regarding turbidity (mean value 1.3 NTU) and suspended solids (mean value 2.1 mg L⁻¹). When WWTP overall plant performance dropped from 90 to 80% (although BOD value stayed below 6 mg O₂ L⁻¹, suggesting unrestricted reuse), solids breakthrough in filtrate was observed. Microorganism removal rates were: total coliforms 60.0%, Escherichia coli 63.0%, Giardia spp. 81.0%, and helminth eggs 62.5%; thus organisms still remained in filtrate. Ultraviolet (UV) disinfection efficiency was 4.1- and 3.8-log for total coliforms and E. coli, respectively. Considering low UV efficiency obtained for helminths and the survival of protozoa and helminths in the environment, effluent quality presents risk to public health if destined for unrestricted urban reuse.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call